Quantitative and Operational Performance Comparison of Multi-Objective Evolutionary Algorithms NSGA-II, MOEA/D, and AGE-MOEA in Water Distribution Network Pressure Management Optimization

Articles in Press, Accepted Manuscript, Available Online from 26 July 2026

https://doi.org/10.22034/iwrj.2026.15067.2646

Farzin Sayad beyranvand, Masoud Shakarami

Abstract Introduction:

Water distribution networks in arid regions face persistent challenges including pressure standard maintenance, infrastructure cost reduction, and water loss management. Iran, with annual precipitation of 240–250 mm, confronts severe water scarcity, making efficient network management critically important. Leakage — an unavoidable phenomenon in distribution systems — is directly governed by network pressure, rendering pressure management a primary strategy for loss reduction (Lambert, 2001). Recent advances in multi-objective evolutionary algorithms have expanded optimization capabilities for water distribution networks. While NSGA-II and MOEA/D have been extensively applied in hydraulic engineering, AGE-MOEA — developed by Panichella (2022) based on non-Euclidean Pareto front geometry approximation — has not previously been evaluated in water distribution optimization contexts, as confirmed through systematic searches of Scopus and Web of Science databases. Furthermore, existing studies predominantly assess Pareto front quality metrics while neglecting the operational implementability of optimization outputs, particularly the stability of pressure-reducing valve (PRV) hourly scheduling patterns under real operating conditions. This study presents a comprehensive two-phase framework integrating hydraulic simulation (WaterGEMS/EPANET) and evolutionary optimization (Python/DEAP/WNTR) to evaluate NSGA-II, MOEA/D, and AGE-MOEA across benchmark networks (Hanoi, Balerma) and the real Poldokhtar western zone network, assessing both Pareto front quality and practical operational feasibility

Materials and Methods:

This study developed an integrated framework combining hydraulic simulation and multi-objective evolutionary optimization across three water distribution networks of increasing complexity: the Hanoi benchmark (34 pipes, 32 nodes, single gravity reservoir), the Balerma irrigation network (454 pipes, 443 nodes, four reservoirs), and the real Poldokhtar western zone network (261 pipes, 206 consumption nodes, one 5,000 m³ gravity reservoir, two pressure-reducing valves). Hydraulic models were initially constructed in WaterGEMS and converted to EPANET 2.2 standard format, with pressure-driven analysis (PDA) implemented through the WNTR library in Python, where nodal demand follows q_i^actual=q_i^demand⋅((P_i-P_i^min)/(P_i^req-P_i^min ))^0.5for P_i^min≤P_i≤P_i^req. The Poldokhtar model was calibrated against field measurements of reservoir outflow and PRV discharge rates, achieving acceptable agreement between simulated and observed values; full nodal pressure calibration was constrained by limited field sensor deployment. Three multi-objective evolutionary algorithms — NSGA-II (dominance-based), MOEA/D (decomposition-based), and AGE-MOEA (geometry approximation-based) — were implemented using the DEAP library with identical computational budgets of 200,000 function evaluations (population N=200, generations=1,000), SBX crossover (pc=0.9, ηc=20), polynomial mutation (pm=1/n, ηm=20), and 30 independent runs with random seeds 1–30. For Hanoi and Balerma, decision variables comprised all pipe diameters selected from discrete commercial sizes, with objectives of minimizing total network cost (Z₁) and pressure deviation from permissible ranges. For Poldokhtar, 53 decision variables encompassed hourly scheduling coefficients of two PRVs (48 variables) and diameters of five selected pipes (5 variables), with three objectives: minimizing total hydraulic penalty from pressure and velocity violations (Z₁), minimizing excess pressure (Z₂), and minimizing the sum of selected pipe diameters (Z₃). Algorithm performance was evaluated using Hypervolume (HV) with reference point r=1.1×fmax and Inverted Generational Distance (IGD) computed against a reference front constructed from all non-dominated solutions across 30 runs of all three algorithms, where higher HV and lower IGD indicate superior performance.

Results and Discussions:

Performance evaluation across three networks revealed distinct algorithmic behaviors reflecting fundamental differences in search mechanisms. On the Hanoi network, NSGA-II achieved the only fully feasible solution with zero pressure deviation at a network cost of $77,551, demonstrating superior capability in navigating tight hydraulic constraints, while AGE-MOEA recorded the highest overall Pareto front quality metrics (HV=4.7, IGD=1.87) and MOEA/D performed weakest (HV=3.6, IGD=3.75) due to its inherent sensitivity to objective scale differences — the Tchebycheff scalarization function becomes dominated by the larger-magnitude cost objective, disrupting convergence toward feasible pressure-compliant solutions. On the large-scale Balerma network (454 pipes, 10⁴⁵⁴ search space), AGE-MOEA maintained its quantitative superiority (HV=0.85, IGD=0.019), followed closely by NSGA-II (HV=0.82, IGD=0.024), while MOEA/D exhibited significant diversity loss (HV=0.61, IGD=0.041), confirming that decomposition-based approaches struggle with high-dimensional design spaces where neighborhood assumptions break down. The Poldokhtar three-objective case produced the most operationally informative results. Pareto front comparison (Z₁: total hydraulic penalty vs. Z₂: excess pressure) revealed that AGE-MOEA dominated NSGA-II across the majority of the objective space in the Z₁ range of 5,750–6,000, delivering lower excess pressure for equivalent hydraulic penalty values, while both algorithms provided substantially wider solution diversity than MOEA/D, which concentrated exclusively in the high-penalty low-excess-pressure region (Z₁>6,050, Z₂≈28,800–29,600) — a computationally significant weakness for multi-objective optimization. Hypervolume convergence analysis (Figure 15) revealed an important distinction: MOEA/D achieved the highest final cumulative HV (4,603,078) compared to NSGA-II (4,089,945) and AGE-MOEA (3,369,721), which does not contradict its weaker Pareto front coverage but reflects its deep convergence within a narrow objective region — a fundamentally different metric capturing exploration history rather than final solution quality. PRV hourly scheduling analysis exposed a critical operational dimension absent from purely quantitative assessments: despite their Pareto front superiority, NSGA-II and AGE-MOEA generated highly oscillatory valve settings fluctuating between 18–23 m within single-hour intervals, with quantitative indicators confirming significantly higher variance, directional change frequency, and oscillation amplitude compared to MOEA/D, which produced conservative near-constant patterns with only minor adjustments — most notably a smooth transition at hour 7 for PRV-1. This operational contrast, supported by the equal-weight MCDM compromise solution extracted from each algorithm's Pareto front, demonstrates that Pareto front quality metrics alone provide an incomplete basis for algorithm selection in real operational contexts: AGE-MOEA is recommended for large-scale design optimization where Pareto coverage is paramount, NSGA-II excels when strictly feasible solutions under tight hydraulic constraints are required, and MOEA/D — despite its quantitative limitations — produces the most operationally stable PRV scheduling patterns suitable for direct field implementation, highlighting a fundamental trade-off between mathematical optimality and engineering practicability that warrants explicit consideration in future water network optimization frameworks.

Conclusion:

This study presented a comprehensive evaluation of NSGA-II, MOEA/D, and AGE-MOEA for water distribution network optimization through an integrated WaterGEMS-EPANET-Python framework. AGE-MOEA demonstrated superior Pareto front coverage in large-scale networks, while NSGA-II proved most effective for constraint-intensive design problems requiring fully feasible solutions. Despite weaker Pareto front diversity, MOEA/D generated operationally implementable PRV scheduling patterns with minimal oscillations, revealing a fundamental trade-off between algorithmic optimality and practical deployability. Algorithm selection should therefore be governed by decision-maker priorities: AGE-MOEA for Pareto quality, NSGA-II for constraint satisfaction, and MOEA/D for operational stability. Quantified leakage reduction requires dedicated pressure-leakage modeling in future research.

Water Resources

Development of a Hydraulic Simulation Model and Performance Analysis of Time- and Flow-Modulated Pressure Reducing Valves for Leakage Reduction in Urban Water Distribution Networks Using WaterGEMS Software.

Articles in Press, Accepted Manuscript, Available Online from 07 October 2026

https://doi.org/10.22034/iwrj.2026.15236.2666

Seyyed Mohammad Kazem Banihashemi Emam gheysi, Ali attarzadeh, Hamide Jafari

Abstract Introduction:

Water distribution networks are vital urban infrastructure, yet a substantial share of the water they carry is lost before reaching consumers as non-revenue water, largely through real leakage from mains, distribution pipes and service connections. Leakage wastes scarce water, raises production and pumping costs, reduces reliability and shortens asset life. Hydraulic pressure is the dominant driver of leakage and pipe bursts, so pressure management is widely regarded as one of the most effective and economical ways to reduce real losses. Calibrated hydraulic models such as Water GEMS allow pressure-control strategies to be tested before field implementation. However, most published studies address large networks or specific hydraulic conditions, and small networks with pronounced elevation differences, particularly in Chaharmahal and Bakhtiari Province, remain little studied. In such networks a single fixed pressure setting can cause excess pressure in low-lying zones and deficits at high points. This study therefore develops and validates a Water GEMS model of the Pordanjan distribution network and compares three pressure-reducing-valve (PRV) strategies, namely fixed-outlet, time-modulated and flow-modulated control, in terms of pressure, leakage reduction and practical feasibility.

Materials and Methods:

Pordanjan, a town in Farsan County, Chaharmahal and Bakhtiari Province, is supplied by gravity from a single concrete ground reservoir at the highest point of the town. The network comprises about 37 km of pipes (25–160 mm; 78% polyethylene, 16% steel, 6% asbestos cement), 207 nodes, roughly 3,000 service connections and six demand zones, serving about 9,400 people (projected 13,700 by 2041). Digital maps, as-built drawings, elevation data, customer locations, demand patterns and field pressure records were obtained from the provincial water and wastewater company, drawn in AutoCAD, checked against GIS data and site surveys, and imported into Water GEMS, where geometric errors were corrected. Hydraulic analysis relied on mass and energy conservation, with the Hazen–Williams equation for head loss.

Real losses were estimated by minimum night flow (MNF) analysis. Night leakage was extended to 24 hours through the pressure–leakage relationship Q = C × P^N1, with N1 = 1.15 and C calibrated from hourly model pressures. Network performance was also expressed by the Infrastructure Leakage Index (ILI).

The model was calibrated by adjusting pipe roughness and demand patterns against pressures recorded every 15 minutes for 48 hours at eight points in zones 1,3, 4 and 6, and was then validated with independent pressure and flow data. Three scenarios were simulated over an extended 24-hour period: (1) constant PRV outlet pressure, selected by a sensitivity analysis of 30–55 m; (2) time-modulated outlet pressure following the daily demand pattern; and (3) flow-modulated outlet pressure adjusted to instantaneous flow and controlled through the critical node in zone 6. All scenarios were constrained by a minimum service pressure of 20 m. Indicators were mean, maximum, minimum and standard deviation of nodal pressure, minimum night flow, daily leakage, annual water saving, and the number of nodes above 50 m or below 20 m. The annual economic value of the saved water was examined by sensitivity analysis at 10, 20 and 30 thousand tomans per cubic meter.

Results and Discussions:

The calibrated model reproduced field behavior well: pressure RMSE was below 5%, and differences between simulated and measured pressure and flow were under 10%. The baseline simulation showed strongly non-uniform pressure, from 15.2 to 67.3 m (mean 41.2 m, standard deviation 11.9 m), with 116 nodes above 50 m and 38 below 20 m. Real losses were about 850 m³/day, roughly 22% of inflow and above the national average of 20–25%. MNF was 10.44 L/s, of which 66.5% (6.94 L/s) was real leakage, and the ILI was 3.8. Losses stem mainly from ageing pipes, corrosion-related cracks and weak joints aggravated by excess pressure, and daily pressure fluctuations impose continual mechanical fatigue on pipes and fittings.

All three scenarios improved on the baseline. A constant outlet pressure of 45 m proved optimal: lower values starved the upper zones, higher values limited leakage reduction. It cut mean pressure from 41.2 to 35.8 m, nodes above 50 m from 116 to 32, and daily leakage from 850 to 715 m³ (15.9%), saving 49,275 m³/year. Its weakness is that pressure stays at 45 m through low-demand night hours, when 30–35 m would suffice, and the setting must be revised as the population grows.

Time-modulated control lowered mean pressure to 33.6 m, night flow to 7.98 L/s and daily leakage to 655 m³ (22.9%), saving 71175 m³/year, while holding about 22 m in zone 6 at peak demand. Its limitations are the need for a programmable valve (20–50% costlier than a simple PRV), periodic re-tuning of the time pattern, and no response to sudden demand changes such as fires or pipe bursts. Flow-modulated control, with set points of about 35–38 m at low flow and 48–50 m at peak flow, gave the best technical performance: mean pressure of 32.1 m, pressure standard deviation of 7.8 m, only 8 nodes above 50 m, and daily leakage of 605 m³ (28.8%), saving 89425 m³/year. However, it requires intelligent controllers, flow sensors and the highest investment.

Pressure reduction did not compromise service, as no node fell below 20 m in any scenario. The sensitivity analysis gave annual benefits of about 0.49–1.48, 0.71–2.14 and 0.89–2.68 billion tomans for the three scenarios, and the ranking did not change with water value. Because equipment costs were unavailable, no payback period was calculated. Considering technical performance, cost and implementation constraints, the time-modulated scenario was judged the most suitable option under present conditions. The findings agree with earlier studies showing that pressure management can cut leakage substantially without extensive pipe replacement.

Conclusion:

A calibrated Water GEMS model proved an effective tool for diagnosing pressure problems and comparing control strategies in the Pordanjan network, where topography causes excess pressure in low zones and deficits at high points. All three PRV strategies reduced excess pressure and leakage (by 15.9%, 22.9% and 28.8%) while keeping service pressure above 20 m. Time-modulated control is recommended in the short term for its balance of leakage reduction and cost, with flow-modulated control as a longer-term upgrade. Continuous monitoring of pressure and minimum night flow is needed to sustain the gains. Future work should use long-term seasonal data, SCADA-based real-time control and life-cycle cost analysis.

Keywords: Leakage, Pressure Management, Water Distribution Network, Water Loss, Water GEMS

Author Contributions:

First author: Data collection and preliminary analysis, and manuscript writing.

Second author: Data analysis, guidance, editing and revision of the manuscript, and verification of results.

Third author: Data analysis, guidance, editing and revision of the manuscript, and verification of results.

Data Availability Statement:

The data of this study are part of the M.Sc. thesis of Seyyed Mohammad Kazem Banihashemi Emam Gheysi (Civil–Environmental Engineering, Faculty of Engineering, Qom University of Technology). Part of the data was obtained from the Chaharmahal and Bakhtiari Provincial Water and Wastewater Company.

Funding:

The authors thank the Chaharmahal and Bakhtiari Provincial Water and Wastewater Company for providing data and information and for financial support of this research.

Ethical Considerations:

The authors observed ethical principles in conducting and publishing this work, including avoidance of data fabrication, falsification, plagiarism and misconduct, and all authors confirm this

Modelling and Hydraulic Analysis of Water Distribution Network of the Bezein Town in the Shiraz city

Volume 12, Issue 3, Winter 2019, Pages 99-108

Akbar Ravan Ghalati, Seyed Hamid Ahmadi

Abstract Analyzing water distribution networks is very important under deficiency of fresh drinking water. Careful analysis of urban water supply systems has been much highlighted than before due to water scarcity and water crisis. Analysis of a water distribution network means that the hydraulic characteristic of a water suppling network should be evaluated to test the efficiency of the water supplying network in delivering water to the determined locations. Indeed, the main goal of construction of a water distribution system is to effectively deliver fresh drinking water to consumers with appropriate quality, quantity, and pressure over time. A high quality water distribution system should consist of some main features including: provide acceptable water quality that should not get deteriorated in the distribution pipes network; supply water at all the intended places with sufficient pressure head and sufficient amount of water during firefighting; be designed in a way that no consumer experiences water supply shut-off during maintenance of any part of the system; and also contain fairly watertight to reduce losses due to leakage.
In this paper, the Bezein water distribution network, located in west of Shiraz, Iran, with a total area of 77 hectares and the occupied area of 34 hectares, with 1907 connection and population of about 7,600 was selected as the case study. The network was simulated with WaterGEMS software. The WaterGEMS is multi-platform software which can model hydraulic and water quality of water distribution systems with the options of advanced interoperability, geospatial model-building, optimization, and management tools. The Bezein town is provided with a 150-millimeter diameter main pipe diverted from a 300-millimeter diameter pipeline that supplies drinking water for Shiraz city. The Bezein water distribution network includes pipelines with diameters of 150, 110, 100, 80 and 63 millimeters, which are made of asbestos, polyethylene, and PVC. An electromagnetic flow meter has recorded the discharge and pressure head of the entering flow to the Bezein town every 15 minutes. Based on the measurements, 471261 cubic meters of water with a pressure head of 60 meters entered the water supply network during 2012, indicating the per capita flow of 170 liters per day. Modeling water distribution system was performed by assigning required amount of water demand to each joint (water delivery location), based on appropriate monthly and hourly demand factors after introducing pipeline network plan of the Bezein water distribution network to the WaterGEMS software. The model has been calibrated according to 8 measured joints in the network with the root mean square error of 6.8 meters of water head. The results of model, including the hydraulic parameters of the water distribution network such as water discharge, velocity of flow in pipes, pressure of flow at joints, energy line, and hydraulic grade line, have been simulated during 2012 in every hour after calibration process.
Analysis indicates that the flow velocity was lower than 0.3 meter per second in more than 95 percent of pipes in the water distribution network, in August as the maximum consumption time of year. The flow velocity of 0.3 m/s is the minimum recommended velocity to prevent sedimentation in pipes of water distribution network based on standards. However, velocity of flow in all of the pipes of the network was lower than the recommended amount in the minimum consumption time of the year according to model analysis. Simulation have shown that pressure head in more than 50 percent of the joints was more than 50 meters which is the recommended pressure value in water distribution network. Low velocity in pipes increases the probability of sedimentation and, on the other hand, the high value of pressure head in pipes leads to leakage and will increase the risk of stress fracture in peak pressure hours of the water distribution network. According to analyses of hydraulic parameters, lack of optimized hydraulic condition in this network is possibly due to the use of high-diameter pipes as large as 150, 110, 100 and 80 mm. Results of this study express the necessity of determining hourly and monthly demand factors in terms of exact consumer needs for designing an optimal water distribution network and also emphasize analysis of water distribution systems with the Extended Period Simulation method, in order to evaluate and modify current problems.

A simulation-optimization model for proper safety management in urban water distribution systems

Volume 8, Issue 1, April 2014, Pages 127-135

Mohammad Reza Bazargan-Lari, Faraz Modiri, Mohammad Reza Nikoo

Abstract Water security is a vital issue that may threat by contaminating drinking water of a city, for example through a terrorist attack. In the absence of a proper managing safety in water distribution system, the number of victims of such terrorist attack can reach to whole of city population. In a passive defense approach, the first step for any integrated public alert system and contaminant controlling is rapid detection of contaminant source. Observations from a set of monitoring points are used to detect the contaminant source. The optimal number of required monitoring points and their pattern is a challenging task that closely depends on the potential injection points, the amount and characteristics of injected pollution. The best monitoring system corresponds to the pattern that minimizes (a) the required number of monitoring points, (b) the affected population at detection instant, and (c) the undetected cases. In this study, the fast multi-objective evolutionary algorithm, NSGA-II, is coupled with the simulation model, EPANET, to find a trade-off curve among the conflicting objectives. Monte Carlo simulation is used to incorporate uncertainties in injected pollution. The Nash bargaining solution is utilized to find the equilibrium point of the obtained trade-off curve. In order to demonstrate the efficiency and capabilities of the proposed methodology, the water distribution network of Lamerd City is modeled and the best monitoring points are determined.

Identification of real water loss and leakage performance indicators in the water distribution network of the Lar city

Volume 8, Issue 1, April 2014, Pages 229-232

Masoud Noshadi, Moslem Rasti

Abstract In this research, a part of the distribution network in Lar city was selected for the calculation of real loss volume and leakage indicators in the network. Magnetic flow meter, data logger, and digital Dickson pressure gauge were installed at the input of the network. The pressure and flow rate were recorded in 15 minutes time intervals. Then, on various stages of research real water loss and leakage performance indicators, including ILI, UBRL and TIRL were calculated. Based on the results, the real water loss was between 12.1-18.7% with an average of 15.5%. The Technical indicator for real losses (TIRL) during measured periods were in the range of 97.2-188.5 lit.d-1.con-1 with the mean of 147.5 lit.d-1.con-1. Unavoidable background real losses (UBRL) were between 34.2-44.6 with the mean of 40 lit.d-1.con-1 and infrastructure leakage index (ILI) was between 2.8-4.2 with the mean of 3.6, which indicate that the network condition is undesirable. The mean recyclable leakage for each connection is 107.5 lit.d-1.con-1, which considering the number of service connections (18100), the total recyclable leakage in water distribution network in Lar city is 710199 m3.year-1.